The SPAJ140 is a versatile, microprocessor-based protection relay manufactured by ABB for medium and high voltage distribution networks. This compact unit combines overcurrent and earth-fault protection functions in a single device, making it ideal for feeder protection in substations and industrial power systems. The SPAJ140 ensures reliable detection of fault conditions and rapid isolation of defective network sections.
.jpg)
.jpg)
There are still some products that have not been listed yet. For more information, please contact us. If the product model does not match the displayed picture, the actual model shall prevail. Please consult us for specific product images; We will arrange for the warehouse to take photos for confirmation. We have 76 shared warehouses worldwide, so it may take several hours to accurately respond to your message. We deeply apologize for any inconvenience caused to you. Of course, we will process your inquiry as soon as possible.
The SPAJ140 is a versatile, microprocessor-based protection relay manufactured by ABB for medium and high voltage distribution networks. This compact unit combines overcurrent and earth-fault protection functions in a single device, making it ideal for feeder protection in substations and industrial power systems. The SPAJ140 ensures reliable detection of fault conditions and rapid isolation of defective network sections.
.jpg)
Model SPAJ140
Manufacturer ABB
Protection Functions Overcurrent (TOC/IOC) + Earth-Fault
Current Input 1A or 5A (selectable)
Operating Voltage 40-265V AC/DC
Frequency 50/60 Hz
Trip Output 2 changeover contacts
Operating Temperature -10°C to +55°C
Protection Class IP20 (front), IP10 (rear)
.jpg)
Configuration: Program the SPAJ140 protection settings via the front panel HMI or serial communication port using ABB's CAP 505 software.
Setting Groups: Select appropriate parameter sets (Setting Group A/B) based on network operating conditions.
Monitoring: Continuously monitor phase currents and residual current through the SPAJ140 display or remote SCADA interface.
Fault Response: Upon detection of overcurrent or earth-fault conditions, the SPAJ140 initiates the programmed tripping sequence and records event data.
Reset: After fault clearance, reset the SPAJ140 indicators manually or automatically as configured.
⚠️ Critical Safety Guidelines:
Ensure all primary circuits are de-energized and isolated before installing the SPAJ140
Verify correct CT polarity connections to prevent maloperation of the SPAJ140 protection functions
Install external shorting blocks on current transformer secondary circuits during wiring work
Confirm auxiliary supply voltage matches the SPAJ140 rated range (40-265V AC/DC)
Maintain minimum clearance distances as specified in the SPAJ140 technical manual
Never operate the SPAJ140 with the front cover removed — risk of electric shock
Maintenance Item | Frequency | Action |
Visual Inspection | Monthly | Check SPAJ140 LED indicators, display clarity, and enclosure condition |
Function Testing | Annually | Perform primary injection tests to verify SPAJ140 pickup and trip times |
Contact Verification | Annually | Test output relay contacts for proper operation and contact resistance |
Settings Review | Bi-annually | Verify SPAJ140 parameter settings match current protection requirements |
Firmware/Software | As needed | Update relay firmware and CAP 505 configuration tools |
No display on SPAJ140 Auxiliary supply failure Check voltage at terminals; verify supply range
Unwanted tripping Incorrect settings or CT wiring Review settings; verify CT polarity and ratio
Failure to trip Setting too high or output relay fault Reduce pickup value; test output contacts
Communication error Wiring or protocol mismatch Check RS-232/RS-485 connections; veri
Do you provide global shipping services?
Yes. We have local distribution centers on all continents, which can quickly transport parts to any corner of the world.
2. What payment methods and currencies do you accept?
To make your purchasing process as simple as possible, we offer multiple payment methods including bank transfer, check, and PayPal. Meanwhile, we also accept most mainstream credit and debit cards, such as Visa, Mastercard, and American Express. We can accept payments in most major currencies worldwide, but we recommend using US dollars (USD), British pounds (GBP), or euros (EUR) as a priority. Payments in other currencies may incur additional fees. All transactions are securely processed by HSBC Bank and HSBC Merchant Services.
How many parts do you currently have in stock?
We have a vast inventory of thousands of new, refurbished, and outdated automation components, including products from well-known manufacturers such as ABB and Schneider. If you cannot find the required parts, please do not worry. We work closely with a global network of professional suppliers to provide you with tailored quotes even if the part is not listed on our website.
Who can I contact if I encounter any problems?
Our experienced customer service team will handle any issues after you place your order.