Acting as a frontline asset defense system, theH201Timounts permanently to a single oil valve to achieve continuous, real-time tracking of thermal and electrical faults.
.jpg)
.jpg)
There are still some products that have not been listed yet. For more information, please contact us. If the product model does not match the displayed picture, the actual model shall prevail. Please consult us for specific product images; We will arrange for the warehouse to take photos for confirmation. We have 76 shared warehouses worldwide, so it may take several hours to accurately respond to your message. We deeply apologize for any inconvenience caused to you. Of course, we will process your inquiry as soon as possible.
The GE Hydran H201Ti represents the fourth generation of compact, valve-mounted asset protection hardware developed to comply with standard IEEE C57.104 early warning frameworks. Positioned as an essential monitoring solution for small to medium-sized transmission and distribution transformers, the unit targets the root causes of insulation degradation before they escalate into high-consequence failure events.
The core detection engine relies on an advanced fuel cell sensor positioned directly behind a gas-permeable, vacuum-resistant membrane. This configuration yields a composite "Hydran Gas Value" in ppm, reflecting a 100% relative sensitivity to Hydrogen (H2) while maintaining targeted sensitivity to Carbon Monoxide (CO from degrading structural paper), Acetylene (C2H2 indicating active arcing), and Ethylene C2H4 indicating severe oil overheating). Utilizing passive Dynamic Oil Sampling driven by natural transformer convection currents, the transmitter continuously refreshes its sampling face without mechanical moving components.
.jpg)
| Parameter | Performance & Structural Details |
| Manufacturer / Brand | GE Vernova / Grid Solutions |
| Model Nomenclature | H201Ti / Hydran 201Ti (Mark IV) |
| Primary Measurement Range | 0 to 2,000 ppm (H2 equivalent volume) |
| System Detection Accuracy | ±10% of reading or ±25 ppm (whichever value is greater) |
| Sensor Baseline Response | 10 minutes to reach 90% of a definitive step change |
| Local Device Interface | Backlit LCD (2 lines x 16 characters) with parameter keypad |
| Local Service Port | 1x Dedicated USB Type B (laptop configuration access) |
| Supervisory Digital Interface | Isolated RS-485 supporting Modbus RTU and Hydran protocols |
| Analog Infrastructure Loop | 1x 4–20 mA current loop (0–2000 ppm range, 10V max load) |
| Discrete Contact Alarms | 3x Form C SPDT dry relays, rated 3A @ 250 VAC / 30 VDC |
| Alarm Trigger Modes | Settable on absolute ppm value OR daily/hourly Rate-of-Change (ROC) |
| Standard Mounting Fitting | Directly matches 1", 1.5", or 2" female NPT valves via adapters |
| Environmental Enclosure | IP66 dust and moisture sealed / NEMA Type 4X certified |
| Input Power Configuration | Field-switchable: 90–132 VAC or 180–264 VAC, 47–63 Hz |
| Physical Net Weight | 5.6 kg (12 lbs) unit only |
.jpg)
Pump-Free Fluid Interactions: Utilizes natural convective oil flow across the internal sampling manifold to remove mechanical failure points like pumps, rotors, and external piping.
Dual Trend Tracking: Tripping mechanisms are independent, allowing operators to trigger early alerts based on standard gas thresholds or sharp hourly and daily gas generation surges.
Multi-Node Networking: Built-in RS-485 line isolation supports daisy-chain network looping of up to 32 individual 201Ti transmitters or auxiliary controllers across distances up to 4,000 feet.
Controller Compatibility: Integrates seamlessly with remote mounting modules like the H201Ci-1 (single-channel display clone) or the H201Ci-C (four-channel data concentrator for single-phase bank setups).
Comprehensive Maintenance Diagnostics: Features automatic execution of an internal self-diagnostic routine every 15 days, immediately engaging a dedicated service alarm in the event of sensor drift, heating failure, or supply interruption.
Substation Asset Management: Deploying low-maintenance monitoring fleets across non-critical transmission nodes to rank asset replacement strategies.
Industrial Facility Subpanels: Protecting high-value rectifiers and furnace transformers inside heavy manufacturing plants from unexpected process interruptions.
Fleet Screening Diagnostics: Serving as an alternative to periodic manual syringe fluid extractions by providing constant live telemetry.
Ester-Based Fluid Deployments: Suitable for modern synthetic and natural ester-insulated transformers as well as standard mineral oils.
Q: What exactly does the composite gas reading represent on the display?
A: The composite reading is the cumulative total value of key fault gases dissolved in the oil.
Q: Can the H201Ti be mounted in cold ambient environments?
A: Yes. The device features an integrated internal heating plate assembly and is certified to operate reliably in ambient temperatures down to -40°C (-40°F).
Q: How does the H201Ti differ from the larger Hydran M2 system?
A: The H201Ti is an essential, single-gas transmitter focused strictly on composite fault-gas profiling.
Q: Is on-site calibration or chemical gas standard injection required?
A: No field calibration is needed. The internal fuel cell architecture and factory certification isolate the device from baseline drift under normal operation, requiring only a mechanical sensor swap every 5 to 7 years depending on site conditions.
Do you provide global shipping services?
Yes. We have local distribution centers on all continents, which can quickly transport parts to any corner of the world.
2. What payment methods and currencies do you accept?
To make your purchasing process as simple as possible, we offer multiple payment methods including bank transfer, check, and PayPal. Meanwhile, we also accept most mainstream credit and debit cards, such as Visa, Mastercard, and American Express. We can accept payments in most major currencies worldwide, but we recommend using US dollars (USD), British pounds (GBP), or euros (EUR) as a priority. Payments in other currencies may incur additional fees. All transactions are securely processed by HSBC Bank and HSBC Merchant Services.
How many parts do you currently have in stock?
We have a vast inventory of thousands of new, refurbished, and outdated automation components, including products from well-known manufacturers such as ABB and Schneider. If you cannot find the required parts, please do not worry. We work closely with a global network of professional suppliers to provide you with tailored quotes even if the part is not listed on our website.
Who can I contact if I encounter any problems?
Our experienced customer service team will handle any issues after you place your order.